PHPTUV2
O:78|T:5|I:2
BLOCK TRIP
PICKUP
PHPTOV2
O:75|T:5|I:2
BLOCK TRIP
PICKUP
NSPTOV2
O:76|T:5|I:2
BLOCK TRIP
PICKUP
ROVPTOV3
O:73|T:5|I:3
BLOCK TRIP
PICKUP
SEQRFUF2_60-2_FUSEF_U
SEQRFUF2_60-2_FUSEF_U
SEQRFUF2_60-2_FUSEF_U
PHPTOV2_59-2_TRIP
PHPTUV2_27-2_TRIP
NSPTOV2_47-2_TRIP
ROVPTOV3_59N-2_TRIP
GUID-9DE7CD91-E7CF-4259-8444-F319579843BC V1 EN
Figure 233: Voltage functions on bus 2
The circuit-breaker failure protection CCBRBRF_50BF is initiated via the PICKUP input
by a functions connected to the Master Trip 1 and by opening command of the circuit
breaker. CCBRBRF_50BF offers different operating modes associated with the circuit-
breaker position and the measured phase and residual currents.
CCBRBRF_50BF has two operating outputs: TRRET and TRBU. The TRBU output can be
used to give a backup trip to the circuit breaker feeding upstream. In the configuration the
TRBU output signal is connected to the output SO1 (X100: 14, 15, 16).
CCBRBRF1_50BF-1 use the source 1 (bus 1) voltages whereas CCBRBRF2_50BF-2 use
the source 2 (bus 2) voltages.