CBXCBR1
O:69|T:5|I:1
POSOP EN
POSCLOSE
ENA_OPEN
ENA_CLOSE
BLK_OPEN
BLK_CLOSE
AU_OPEN
AU_CLO SE
TRIP
SYNC_OK
SYNC_ITL_BYP
SELECTED
EXE_OP
EXE_CL
OP_REQ
CL_REQ
OPENPOS
CLOSEPOS
OKPOS
OPEN_ENAD
CLOSE_ENAD
CBXCBR2
O:46|T:5|I:2
POSOP EN
POSCLOSE
ENA_OPEN
ENA_CLOSE
BLK_OPEN
BLK_CLOSE
AU_OPEN
AU_CLO SE
TRIP
SYNC_OK
SYNC_ITL_BYP
SELECTED
EXE_OP
EXE_CL
OP_REQ
CL_REQ
OPENPOS
CLOSEPOS
OKPOS
OPEN_ENAD
CLOSE_ENAD
NOT
O:113|T:2.5|I:2
IN OUT
NOT
O:43|T:2.5|I:3
IN OUT
Control
O:4|T: 2.5|I:0
CTRL_OFF
CTRL_LOC
CTRL_STA
CTRL_REM
CTRL_ALL
OFF
LOCAL
STATION
REMOTE
ALL
BEH_TEST
BEH_BLK
CBXCBR1_52-1_EXE_CL
CBXCBR2_52-2_EXE_CL
CB2_POSITION_CLOSE
CB1_POSITION_CLOSE
TRPPTRC1_86_94-1_TRIP
CBXCBR1_52-1_EXE_OP
TRPPTRC2_86_94-2_TRIP
CBXCBR2_52-2_EXE_OP
CB1_POSITION_OPEN
CB2_POSITION_OPEN
GUID-ACF312FD-FAE1-4AF9-9727-EA5701905F3D V1 EN
Figure 244: Circuit breaker control
If the ENA_CLOSE and BLK_CLOSE signals are completely removed from the breaker
control function block CBXCBR_52 with PCM600, the function assumes that the breaker
close commands are allowed continuously.
The sync check function SECRSYN1_25 is provided in this standard configuration. The
main purpose of the synchronism and energizing check is to provide control over the
closing of the circuit breakers in power networks to prevent the closing if the conditions
for synchronism are not detected. The energizing function allows closing, for example,
when one side of the breaker is dead.
The sync check function measures the bus and line voltages and compares them to set
conditions. When all the measured quantities are within set limits, the output SYNC_OK is
activated for allowing closing of the circuit breaker. The SYNC_OK output signal of
SECRSYN1_25 is connected to ENA_CLOSE input of CBXCBR1_52-1.
By default, Bus 1 is designated as the bus side and Bus 2 as the line side. Thus, LLDB
means that Bus 2 is live and Bus 1 is dead; similarly, LLLB means that both Bus 2 and 1