Circuit breaker failure protection CCBRBRF1_50BF-1 is initiated via the PICKUP input
by number of different protection functions available in the relay. The breaker failure
protection function offers different operating modes associated with the circuit breaker
position and the measured phase and residual currents.
The circuit breaker failure protection function has two operating outputs: TRRET and
TRBU. The TRRET trip output is used for retripping its own breaker through
TRPPTRC2_86/94-2_TRIP. The TRBU output is used to give a backup trip to the breaker
feeding upstream. For this purpose, the TRBU trip output signal is connected to the binary
output X100:PO2.
CCBRBRF1
O:44|T:2.5|I:1
BLOCK
PICKUP
POSCLOSE
CB_FAULT
CB_FAULT_AL
TRBU
TRRET
OR6
O:26|T:2.5|I:1
B1
B2
B3
B4
B5
B6
O
OR6
O:27|T:2.5|I:0
B1
B2
B3
B4
B5
B6
O
OR6
O:29|T:2.5|I:2
B1
B2
B3
B4
B5
B6
O
CCBRBRF1_50BF-1_TRBU
X120_BI2_CB_CLOSED
PHIPTOC1_50P-3_TRIP
DPHHPDOC1_67/50P-1_TRIP
DPHLPDOC1_67/51P-1_TRIP
EFPADM2_21YN-2_TRIP
EFPADM3_21YN-3_TRIP
DEFHPDEF1_67/50N-1_TRIP
DEFLPDEF2_67/51N-2_TRIP
WPWDE2_32N-2_TRIP
WPWDE3_32N-3_TRIP
ARCSARC1_AFD-1_T RIP
ARCSARC2_AFD-2_T RIP
ARCSARC3_AFD-3_T RIP
CCBRBRF1_50BF-1_TRRET
GUID-A783E6FC-1967-44F0-8452-D9D913556E2B V1 EN
Figure 64: Circuit breaker failure protection function
Three arc protection stages ARCSARC-1…3_AFD-1...3 are included as an optional
function. The arc protection offers individual function blocks for three arc sensors that can
be connected to the relay. Each arc protection function block has two different operation
modes, that is, with or without the phase and residual current check.
The trip signals from ARCSARC-1…3_AFD-1...3 are connected to both trip logic
TRPPTRC1_86/94-1 and TRPPTRC2_86/94-2.