SEQSPVC1
O:28|T:2.5|I:1
BLOCK
CB_CLOSED
DISCON_OPEN
MINCB_OPEN
FUSEF_3PH
FUSEF_V
X120_BI2_CB_CLOSED SEQSPVC1_60-1_FUSEF_U
X110_BI1_MCB_OPEN
SEQSPVC1_60-1_FUSEF_3PH
GUID-5B3039E4-0E32-40F3-A0BB-F358206E44F0 V1 EN
Figure 78: Fuse failure supervision function
Circuit-breaker condition monitoring SSCBR1_52CM-1 supervises the switch status
based on the connected binary input information and the measured current levels.
SSCBR1_52CM-1 introduces various supervision methods.
Set the parameters for SSCBR1_52CM-1 properly.
SSCBR1
O:90|T:5|I:1
BLOCK
POSOPEN
POSCLOSE
OPEN_CB_EXE
CLOSE_CB_EXE
PRES_ALM_IN
PRES_LO_IN
SPR_CHR_ST
SPR_CHR
RST_IPOW
RST_CB_WEAR
RST_TRV_T
RST_SPR_T
TRV_T_OP_ALM
TRV_T_CL_ALM
SPR_CHR_ALM
OPR_ALM
OPR_LO
IPOW_ALM
IPOW_LO
CB_LIFE_ALM
MON_ALM
PRES_ALM
PRES_LO
OPENPOS
INVALIDPOS
CLOSEPOS
CB_CLOSE_COMMAND
CB_OPEN_COMMAND
X120_BI3_CB_OPEN
X120_BI2_CB_CLOSED
SSCBR1_52CM-1_TRV_T_OP_ALM
SSCBR1_52CM-1_TRV_T_CL_ALM
SSCBR1_52CM-1_SPR_CHR_ALM
SSCBR1_52CM-1_OPR_ALM
SSCBR1_52CM-1_OPR_LO
SSCBR1_52CM-1_IPOW_ALM
SSCBR1_52CM-1_IPOW_LO
SSCBR1_52CM-1_CB_LIFE_ALM
SSCBR1_52CM-1_MON_ALM
SSCBR1_52CM-1_PRES_ALM
SSCBR1_52CM-1_PRES_LO
GUID-2ACB76D8-D894-4B01-BAC4-C11817D98201 V1 EN
Figure 79: Circuit-breaker condition monitoring function
OR6
O:91|T:2.5|I:24
B1
B2
B3
B4
B5
B6
O
OR6
O:92|T:2.5|I:23
B1
B2
B3
B4
B5
B6
O
OR
O:93|T:2.5|I:12
B1
B2
O
SSCBR1_52CM-1_TRV_T_OP_ALM
SSCBR1_52CM-1_TRV_T_CL_ALM
SSCBR1_52CM-1_SPR_CHR_ALM
SSCBR1_52CM-1_OPR_ALM
SSCBR1_52CM-1_OPR_LO
SSCBR1_52CM-1_IPOW_ALM
SSCBR1_52CM-1_IPOW_LO
SSCBR1_52CM-1_CB_LIFE_ALM
SSCBR1_52CM-1_MON_ALM
SSCBR1_52CM-1_PRES_ALM
SSCBR1_52CM-1_PRES_LO
SSCBR1_52CM-1_ALARMS
GUID-DE2C5247-1CB4-4417-9A13-8854E815A237 V1 EN
Figure 80: Logic for circuit breaker monitoring alarm
Two separate trip circuit supervision functions are included: TCSSCBR1_TCM-1 for
power output X100:PO3 and TCSSCBR2_TCM-2 for power output X100:PO4. Both the
1MAC109016-MB C Section 3
REF615 standard configurations
REF615 ANSI 89
Application Manual