Indicator Code Source / Root Cause Possible Cause / Suggested Action
AM1 >/< level trip 28 Value on sensor >/< configured
level
AI111 module; more details see under code no. 146..157
AM1 >/< level warn 29 Value on sensor >/< configured
level
AI111 module; more details see under code no. 146..157
AM2 >/< level trip 30 Value on sensor >/< configured
level
AI111 module; more details see under code no. 146..157
AM2 >/< level warn 31 Value on sensor >/< configured
level
AI111 module; more details see under code no. 146..157
Warning LCD panel missing 32 If Auto Save is configured Connect panel or deactivate Auto Save
Underload Power 34 Load side mechanics The motor load is too low. Check the load e.g. if a pump is running
dry or a conveyer load is broken.
Overload Power 35 Load side mechanics The motor load is too high. Check if the load is blocked or tight.
Voltage Out of Spec 36 Load side The supply voltage is too low or too high. Check the motor supply.
THD Warning 37 Supply side The harmonics on the supply side are too high. Check your network.
Num Starts Overrun 43 Application The motor was started too frequent.
Just One Start Left 44 Application The motor was started too frequent.
Cooling time running 45 Process, Load side Motor was tripped due to thermal overload. Restart is possible
after cooling time is over
Parameter out of range 54 Electronics, Configuration Someone tried to write a parameter which is outside the
specifications
Check the parameter number that is causing the problem and
change the value.
When writing parameters from within a PLC check your program.
Torque open in intermediate
position
64 Actuator mechanics Tight operation or wiring problem.
Torque close in intermediate
position
65 Actuator mechanics Tight operation or wiring problem.
Pos. open and closed at same
time
66 Actuator mechanics Wiring / position switch problem
End pos. open not left within
specified time
67 Actuator mechanics Wiring / position switch problem or wrong adjustment of position
switch.
End pos. closed not left within
specified time
68 Actuator mechanics Wiring / position switch problem or wrong adjustment of position
switch.
End position open without
command
69 Actuator mechanics Wiring / position switch problem.
End position closed without
command
70 Actuator mechanics Wiring / position switch problem.
Left pos. open without
command
71 Actuator mechanics Wiring / position switch problem.
Left pos. close without
command
72 Actuator mechanics Wiring / position switch problem.
Motor operation hour exceeded 74 Load side mechanical Max. motor operation hours reached.
Perform motor maintenance
Reset counter
Wrong password 76 Electronics
Line frequency out of range 77 Supply side Check supply
Wrong phase sequence
(reversal)
78 Supply side,
Load side
Phase order is not L1/L2/L3.
CB relay 0 80 Wiring,
Contactors
Expected feedback from a contactor is missing after checkback
time was over.
Check wiring of auxiliary contact to the correct UMC input.
Check contactor
Increase checkback time
CB StarDelta via Current 81 Contactors, Supply side, Load side special case of code no 82
CB current 82 Contactors,
Supply side,
Load side
No motor current after motor was switched on and checkback time
was over. Or motor current falls below 20% while motor is running.
Check supply side
Check that I
e
was set correctly
Check current factor if set
Increase checkback time
115