Limit
Open
Limit
Closed
M
Torque
Open/
Closed
Control Function Actuator 1 - 4
Use this function in a feeder that requires the operation of an actuator that opens/closes e.g. a valve. Please note that the actuator
operation mode is not able to keep a valve at a certain setpoint.
The voltage dip function is not supported and checkback via DIO is not supported in these control functions.
Set the following parameters as listed here:
• Inv DI start input = No
• Inv DI stop input = No
• Inching DI start input (Jog) = Yes
• Multifunction 0/1 = Off
• Checkback: Current or Simulation (test purposes only)
• Adjust Time Limit Actuator
—
Control function = Actuator 2 (Basic circuit)
The control functions Actuator 1, 2, 3 and 4 provide different use of and reaction to the limit switches “Closed” and “Open” as well
as the torque switches. The switches must be connected in a predefined manner to DI0, DI1 and DI3.
Optionally terminals named 24VDC Out (12) or DO2 can be used as a fault output
86