Earth Fault Trip
Vectorsum
> Trip Thresh.
I
L1
I
L2
I
L3
Ton
Vectorsum
> Warn Thresh.
Ton Earth Fault Warning&
&
>
Always
After
start-up
Protection based on internal Calculation
The UMC can detect an earth fault by summing up the three phase currents without using an external current transformer. The inter-
nal earth fault detection function signals a warning when the earth fault current exceeds a set threshold for a configurable period
of time, after the motor start-up. The earth fault detection function creates a trip when the current continuously exceeds a separa-
tely set threshold for a set period of time, after the motor start-up.

e
to be detected
Only usable in networks with low impedance to ground.
Only higher ground fault currents can be detected

e
In case of fast starting motors without load an earth fault trip can happen during the start-up phase. Configure a
delay time in this case.
Block Diagram:
Signal flow of the internal earth fault protection function
Relevant Parameters Internal Ground Fault:
Earth Flt Trip Level Earth Flt Warn Level
Earth Flt Trip Delay Earth Flt Warn Delay
Earth Flt Detection


47