Monitoring Data for Pole-Changing Starter
Word Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit1 Bit 0
0
0 Summary
Warning
Summary
Fault
Local Con-
trol
- Overload
warning
Run
Forward
Off -
1 UMC100
DI5
UMC100
DI4
UMC100
DI3
UMC100
DI2
UMC100
DI1
UMC100
DI0
Run
Fast
Forward
-
1 2, 3 Motor Current in % of I
e
(0% - 800%)
2 4, 5
Remaining data see section Parameters and Data Structures on a Fieldbus
3 6, 7
4 8, 9
5 10.11
6
12
13
7
14
15
The table above represents the data allocation as realised with the built-in standard applications. It may differ for
customer-specific applications!
Command Data for Pole-Changing Starter
Word Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit1 Bit 0
0
0 - Fault Reset Auto Mode Prepare
Emergency
Start
- Run
Forward
Off -
1 UMC100
DO2
1)
- - UMC100
24VDC
Out
1)
- - Run
Fast
Forward
-
1
2
Remaining data see section Parameters and Data Structures on a Fieldbus
3
2 4, 5
3 6, 7
1)
Controlled by UMC100 if configured as fault output.
The table above represents the data allocation as realised with the built-in standard applications. It may differ for
customer-specific applications!
85