Indicator Code Source / Root Cause Possible Cause / Suggested Action
OK Stamp 128 OK Stamp not correct or missing Hardware fault detected during selftest
Replace UMC
Abgl. Checksum 129 Calibration checksum
FRAM read/write 130 FRAM error
Param D invers 131 Parameter storage error
Thermal capacity 132 Thermal capacitor error
VCC voltage 133 VCC voltage
12VP voltage 134 12VP voltage
12VN voltage 135 12VN voltage
PTC channel 136 PTC_Channel
Flash Checksum 137 Flash Checksum in microprocessor
curr. meas. channel 139 current measure channel
Selftest UMC_HW1 140 Summery fault
(RAM, CPU, ….)
Voltage DIP 144 Undervoltage / no voltage
situation is too long
The DIP took longer than configured in parameter Voltage Dip
Duration
Parameter up/download 145 A problem occured during
parameter exchange between the
UMC and the LCD panel.
Check that the parameters / application stored in the LCD panel
can be handled from the used UMC.
Do not remove the panel while parameter exchange
Do not remove power while parameter exchange.
AM1 CH1/2/3 HH/H
AM2 CH1/2/3 HH/H
146,148,150
152,154,156
Value on senser > configured
HH/H level
Check process
AM1 CH1/2/3 LL/L
AM2 CH1/2/3 LL/L
147,149,151
153,155,157
Value on senser < configured L/LL
level
Check process
AM1 max. temperature
AM2 max. temperature
158
159
In temperature mode:
Temperature of one of the sensors
connected to
AM1 is above configured maximal
temperature
Check motor/process conditions
Motor stand still hours
exceeded
160 Motor did not run for a long time Start motor to check everyting is still fine
Error parameter inverters
invers
161 Invalid parameter from auto save Load correct parameters
117
ERROR HANDLING, MAINTENANCE AND SERVICE

Table of Contents

Related product manuals