Parameter
Number
Parameter Description, Explanations Options Adjustable
via
Limit the Number of Starts
 Num Starts Allowed 
time window.

Zero switchs off the start limit
function.


 Num Starts Window 
number of starts are allowed.





 Num Starts Pause After the motor was stopped a new start is not
possible before the pause time is over.. This
paramter can be used independantly of the other
parameters i.e. without limiting the number of
starts in a time window.





 Num Starts Overrun Reaction if no start is left anymore but a start
command was issued.





 Num Starts Prewarn Reaction if only one start is left. 




Maintenance related parameters
 Motor operating hours level After the defined number of weeks of motor
operation a warning is triggered.


supervision
All
 Motor stand still level After the defined number of weeks of continous
motor stand-still time a warning is triggered.
Motor Management Parameters Continued
126