Parameter
Number
Parameter
Name
Description, Explanations Options Adjustable via
Phases
Phase loss
protection
Trips the motor depending of the trip class withinseconds
in case of a phase loss. This parameter must be set to On during
regular operation.
Note: If the voltage module
is present this parameter
activates both voltage and
current based phase loss
detection.
All
Curr Imb Trip
Level
generated. This function is activated together with the phase
loss protection.
Curr Imb Warn
Level
warning is generated. This function is activated together with the
phase loss protection.
Phase
reversal
If enabled the three phases must be fed through the UMC CTs in
Note: If the voltage module
is present this parameter must
not be changed.
Check phase
sequence
Note: If the voltage module
is present this parameter
activates both voltage and
current based phase sequence
protection.
Low curr trip
level
Value in % of I/I
e
. Below this value a trip is generated. A value of
All
Low curr warn
level
Value in % of I/I
e
. Below this value a warning is generated. A value
All
Low curr trip
delay
Low curr warn
delay
High curr trip
level
Value in % of I/I
e
. Above this value a trip is generated. A value of
All
High curr warn
level
Value in % of I/I
e
. Above this value a warning is generated. A value
All
High curr trip
delay
High curr warn
delay
Protection Parameters Continued
128