Table A.4: EMC Specifications - 1
(Continued)
Design Level/Acceptance CriteriaStandardsCategory/Purpose
4 kV (line to ground)EN 13611
Others:
2 kV (line to ground)
10 V (150 kHz to 80 MHz, 1 kHz (80 %
AM))
IEC 61000-4-6
IEC 61326-3-1
Conducted Disturbances Immunity,
induced by radio-frequency fields
EN 13611
30 A/m cont., 300 A/m for 1sIEC 61000-4-8Magnetic Field Immunity
EN 13611
Table A.5: EMC Specifications - 2
Design Level/Acceptance CriteriaStandardsCategory/Purpose
Severity Level 3IEC 61000-4-16Conducted, Common Mode Disturbances
Immunity
1 V to 10 V, 20 dB/Decade (1,5 kHz to 15
kHz)
IEC 61326-3-1
10 V (15 kHz to 150 kHz)
10 V (DC, 16 2/3 Hz, 50/60 Hz and
150/180 Hz)
100 V short duration (1s, DC, 16 2/3 Hz
and 50/60 Hz)
Voltage dips: 40% and 70% UT for 10msIEC 61000-4-29Voltage Dips and Interruptions Immunity
Short interruption: 0% UT for 10ms and
20ms
IEC 61326-3-1
EN13611
0V and Recorded Voltage to 10%
CISPR 11:2015/AMD1:2016IEC 61000-6-4Radiated Emission and Conducted
Emissions
CISPR 16-1-1:2015
Group1, Class A, ISM Equipment