Network Type
The default value is “MOD” which indicates that MODBUS protocol is used.
MOD Address
Set the MODBUS address for RS-485 output to be an integer value between 1 and 254.
Each SF910i RS-485 output on a network must have a unique address.
MOD Baud Rate
Set the baud rate for the RS-485 outputs to be one of the following values:
9.6 = 9,600 bps
19.2 = 19,200 bps
38.4 = 38,400 bps
115.2 = 115,200 bps
8.3.7 Display Options
The user can customize the LCD display for the environment.
Contrast - Increase or decrease the LCD contrast setting to optimize the visibility of the
display.
8.3.8 Complete Reset
The user can reload all the default values for both the program and configuration modes
using the option.
The only values that are not reset with this option are Channel IDs.