Appendix K Program-Mode Fucntions
Table K.1: Program-Mode Functions
Values AvailableDefault ValueLevelProgram Function
FSAFSAFunction Set to Edit
CH FSET TO EDIT
FSB (if used)
FSC (if used)
FSD if used)
5 to 8030Pull-In
Intensity
Trip Points
Pull-In - 6 maximum30Drop-Out
100 to Pull-In + 10100High Limit
5 to 100 or 5 to 225
for turbine
5Pull-In
Frequency
Pull-In - 6 maximum5Drop-Out
125 to Pull-In + 10 or
250 to Pull-In + 10 for
turbine
125High Limit
0 to 800Pull-In
AC-Amplitude Pull-In - 6 maximum0Drop-Out
100 to Pull-In + 10100High Limit
1 to 10020Intensity
Qulaity normalization
1 to 1005Intensity high
1 to 10020Frequency
1 to 1005Frequency high
1 to 10020AC-Amplitude
5 to 1005AC-Amplitude high
5 to 10055N/AFrequency sensitive
None, 1 - 10NoneIntensity
Smoothing (Rolling
Average)
None, 1 - 102Frequency
8VZZ005286 B 187
K Program-Mode Fucntions