34ZBTS_30-1200A rev.A / 1SCC303043M0201
1
For more information of OX_ Automatic
Transfer Switches, see manual:
Automatic transfer switches
TruONE™ ATS, OX_ 30. . .1600_,
34OX_30-1600 / 1SCC303011M0201
00:14
TruONE ATS
Bypass System Overview
G
ATS Status
Connected
Test
Isolated
Bypass Status
Connected
Test
Isolated
Fig. 3.34 Position and location indications on the both
HMIs
5 Operate ATS to same source as
Bypass switch. Now both switches
are connected to the same power
source for a while. This operation will
move at the same time the Bypass
switch automatically from Operation
mode: Auto to Operation mode: MAN
permanent.
Lamp
test
l
ON
Off
load
test
ll
ON
Auto
Alarm reset
On
load
test
Bypass
time
delay
O
OFF
Manual
retransfer
Auto
config
Priority
In-phase
monitor
AUTO
!
S1 S2
LOAD
ll
O
l
Fig. 3.35 The Bypass switch position is seen on the
HMI of Bypass switch –> HMI of ATS; ATS operated
to the same position, see the picture below
l
ON
ll
ON
O
OFF
Fig. 3.36 If the power supply of Bypass switch is Source 1,
the ATS position will be the the same as Bypass switch by
pressing "I ON" button in HMI of ATS
6 Operate Bypass switch to OFF-
position as shown in the Fig. 3.36.
l
ON
ll
ON
O
OFF
Fig. 3.37 Operation of the Bypass switch to
OFF position by pushing the "O OFF"push
button on the HMI of Bypass switch.
7 Set ATS to AUTO-mode by the HMI of
ATS (–> Main Menu –> Operation
mode –> AUTO), see paragraph 3.3.1.3
Main Menu.
NOTE! Make sure the ATS is left in AUTO-
mode after performing any service.