Zenith ZBTS T-series 100-1200A, INSTALLATION AND OPERATING INSTRUCTION
3
9.3.5 DIP switch configuration when
installing Ekip Signalling 10K module
At installation, the module must be con-
figured to communicate via Local Bus or
Link Bus.
With communication via Local Bus, a
-
serted on the communication lines. This

the ON-position by the DIP switch 1 posi-
tioned on the upper side of the module:
DIP
Switch
Termination resistor
No Yes
OFF ON
Table 9.8 Inserting the termination resistor ON
The Ekip Signalling 10K module config-
ured for a basic module 10K-1 is already
done in the factory; configuration is done
with the DIP switches 2 and 3, both are in
OFF-position, see the Fig. 4.14. The DIP
switches are positioned on the upper side
of the module. The following tables de-
scribe the possible configurations, 10K-2
and 10K-3 configurations are not available
for Bypass-Isolation automatic transfer
switch:
DIP
Switch
Ekip Signalling LinkBus
10K-1 10K-2 10K-3
OFF ON OFF ON
OFF OFF ON ON
Table 9.9 Configurations
Fig. 9.9 Ekip Signaling 10K module; When using a local

to the ON position with DIP switch 1. By default,
the Ekip Signaling 10K module type is already 10K-1
position (= DIP switches 2 and 3 are on OFF-position)
NOTE! The operational configuration is
read only at power on. Therefore, if the
module is on, it must be turned OFF and
ON in order for it to recognize a new
configuration.