Zenith ZBTS T-series 100-1200A, INSTALLATION AND OPERATING INSTRUCTION
1
3.3.1 Start Menu
TruONE ATS
Overviews
Main Menu Measures
Analog Meters
Switch Overview
—
Fig. 3.8 By touching on one of Start Menu choices,
you can choose the Overviews -pages (upper left
corner), Main Menu -pages (lower left corner),
Analog Meters -pages (upper right corner) or
Measures -pages (lower right corner)
—
Fig. 3.9 By touching on Start Menu upper left corner
-image you can move to the Overviews -pages, where you
will find Switch status and Supply info views, see the table
below. Switch Overview page shows switch own status.
Switch Overview (Switch status)
Shows voltages and frequencies of both supplies and the switch locations.
Supply info view
Shows voltages and frequencies of both supplies.
Temperature view
Shows the HMI, device and pole temperatures.
HMI temperature indicates ambient temperature where the ATS power panel is installed, when
HMI is mounted to door.
Device temperature indicates the temperature inside the ATS power panel.
Pole temperature indicates the temperature on the load side terminals.
Synchronization view (Enabled only when In-phase monitor is on)
Show the time to next sync, sync period.
Contact Wear
Shows current contact wear information, End of life prediction date and bar graph of the contact wear to
show when replace is needed.
Draw-out locations
Shows switch draw-out locations.
Bypass System Overview
Left side shows ATS draw-out location status and right side shows Bypass draw-out locations status.
3.3.1.1 Overviews
TruONE ATS
Overviews
Main Menu Measures
Analog Meters
Switch Overview
S1 Connected to Load
ATS Connected
Load Current
.... A
14:11
G
TruONE ATS
Switch Overview
S1 p Ok Ok S2
—
Fig. 3.9
—
Fig. 3.8