Zenith ZBTS T-series 100-1200A, INSTALLATION AND OPERATING INSTRUCTION
7.2.3 Ground Connections with Screw
Type Terminals
ABB Zenith Bypass-isolation automatic
transfer switches are supplied with UL
listed solderless screw-type ground ter-
minal as optional choice. Ground terminal
is always factory-mounted and it is situ-
ated on the top module of Bypass-isola-
tion transfer switch, see Fig. 7.7.
Fig. 7.7 Ground terminal is situated on the top module
of Bypass-isolation transfer switch.
Fig. 7.8 Screw-type terminal as optional
choice for the ground connections
7.2.4 Neutral Connections with Screw
Type Terminals
ABB Zenith Bypass-isolation automatic
transfer switches are supplied with UL
listed solderless screw-type neutral termi-
nal as optional choice. Neutral terminal is
always factory-mounted and it is situated
on the top module of Bypass-isolation
transfer switch.
Fig. 7.9 Screw-type terminal as optional
choice for the neutral connections
7.2.5 Conduit Area, Top Cable Entry
The conduit area for top cable entry of the
cabinet must be done in such a way that
the cables can be brought as directly as
Fig. 7.10 The conduit area for top cable entry