Page #79 background image
www.accuenergy.com
V: 1.0 Revised: Jan. 2018
72
AcuDC 240 Series
DC Energy & Power meters
Address (Hex) Address (dec) Parameter Range Data Type Property
0300H- 0301H 768- 769 Import energy 0 ~ 999999999 long R/W
0302H- 0303H 770- 771 Export energy 0 ~ 999999999 long R/W
0304H- 0305H 772- 773 Total energy 0 ~ 999999999 long R/W
0306H- 0307H 774- 775 Net energy
0 ~ ±
999999999
long R/W
0308H- 0309H 776- 777 Import Ah 0 ~ 999999999 long R/W
030AH- 030BH 778- 779 Export Ah 0 ~ 999999999 long R/W
030CH- 030DH 780- 781 Total Ah 0 ~ 999999999 long R/W
030EH- 030FH 782- 783 Net Ah
0 ~ ±
999999999
long R/W
Parameter Relationship Unit
Voltage Real=Rx V
Current Real=Rx A
Power Real=Rx kW
Energy Real=Rx/100 kWh
Ah Real=Rx/100 Ah
AO Real=Rx
V or mA(depends on the AO
Type)
Running Time Real=Rx/100 Hour
Energy
The data space below is for energy;
Function Code: 03 Read; 16 Write
Table B-16 Energy and Charge (Ah) Address Table
The relationship between the register value and the real value (Rx is the register value).
Table B-17 The relationship between Register Value and Real Value

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AccuEnergy AcuDC 241 and is the answer not in the manual?

AccuEnergy AcuDC 241 Specifications

General IconGeneral
BrandAccuEnergy
ModelAcuDC 241
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals