Power-Up Mode
2 7 0
The system will power-up in the same operating mode that was selected
when last powered-down. All inputs are momentary. This is the default
setting.
2 7 1
The system will power-up in Manual mode. All inputs are momentary.
2 7 2
The system will power-up in Servo-Center mode. All inputs are
momentary.
2 7 3
The system will power-up in Automatic mode. All inputs are momentary.
2 7 4
The system will power-up in Manual mode. All inputs are maintained.
2 7 5
The system will power-up in Manual mode and Edge A (Input A) will be
selected. All inputs are momentary.
2 7 6
The system will power-up in Manual mode and Edge B (Input B) will be
selected. All inputs are momentary.
2 7 7
The system will power-up in Manual mode and Line (Input C) will be
selected. All inputs are momentary.
2 7 8
The system will power-up in Manual mode and Edge A and Edge B will
be selected (Centerline mode). All inputs are momentary.
Note: This parameter also affects the operation of the Discrete Isolated Inputs (page 46).
Parameter 28 is reserved for future use.
System ID
2 9 x x x x x
This parameter displays the system ID number.
Password
3 0 0
This parameter is used for enabling optional software features. To
purchase and install optional features, contact AccuWeb for assistance.
Range: 0 to 255
Note: To see which features are enabled, set parameter 29 to 1. The displayed data value
indicates which feature is enabled: 0 = none, 1 = oscillation, 2 = web width monitor, 4 = integrator.
43 for a description of parameters 31, 32, 33, and 34. Refer to page
MICRO 4000
NET Controller
23