Page 23 of 42
The display will revert to the status mode display after 60 seconds on no activity (15 seconds in a
fire alarm condition). Press the Menu button again to return to the menu option. A programmable
timer can be configured to automatically cancel Level 2 access.
3.1.5 Numeric data entry
Numbers are entered by moving to the required field, and then typing in the required number,
followed by the button. The display returns to the previous menu.
If the number is entered incorrectly, press the Í button to clear the entry and then re-enter the
required number. Alternatively, press the ‘Esc’ button to cancel the number entry and return to
the previous menu.
3.2 Recommended Programming Procedure
It is recommended that the configurable options be programmed in the following sequence:
• Configure General Options and Passwords
• Configure the Extinguishing Output Type and Cause & Effect Rule
• Configure the Detection Zone Input Circuits
• Configure the Alarm Outputs and Cause & Effect Rule
• Configure any other Input / Output Circuits
3.3 Level 3 Menu Functions
The following table gives a list of the Level 3 Menu Functions and a brief description for each
function.
Menu Option Sub Menu Comments / Description
3 DETECTION ZONE 1
ZONE 2
ZONE 3
Configuration of the Detection Zone Input Circuits
4 ALARM OUTPUTS SOUNDER 1
SOUNDER 2
SOUNDER 3
PULSE PATTERN
Configuration of the Alarm Sounder Output Circuits and
pulsing operation
OUTPUT SET-UP Configuration of the Actuator Output Circuit
CAUSE & EFFECT Configuration of the release cause and effects rule
2 EXTINGUISHING
EXTRACT SET-UP Configuration of the Extract Output
5 INPUTS Configuration of the Programmable Input Circuits
5 OUTPUTS Configuration of the Programmable Output (Relay) Circuits
1 PASSWORDS Configuration of the Engineer and User Passwords
1 GENERAL Configuration of General parameters
5 STATUS INDICATORS Configuration of any Remote Status Indicator Panels
ENABLE P.C. LINK Permits the connection of a PC for upload of a logo or
download of the configuration and log files.
EXIT Leave the Commission Menu
To enter the Commissioning / Programming Menu, select the COMMISSION option in the Level 2
Menu and press the button. The display prompts for the Level 3 password.
To exit from the Commissioning / Programming Menu, select the EXIT option and press the
button. The display prompts for the Level 3 password.