Parameter Comments / Description Options Default
Setting
ALERT PULSE ON Specifies the Sounder ON period during an ALERT
condition.
1 – 7 Seconds
1
ALERT PULSE OFF Specifies the Sounder OFF period during an ALERT
condition.
1 – 7 Seconds
1
HOLD PULSE ON
12
Specifies the Sounder ON period during the HOLD
condition.
1 – 7 Seconds
1
HOLD PULSE OFF
12
Specifies the Sounder OFF period during the HOLD
condition.
1 – 7 Seconds
2
3.3.3 Extinguishing
The Extinguishing Menu comprises three separate sub-menus. These cover the operating
parameters of the actuator output (Output Set-Up), the fire alarm and manual conditions required
to activate the output (Cause & Effect) and operating parameters for any Extract output (Extract
Set-Up).
[Extinguish Select]
Output Set-Up .
Cause & Effect
Extract Set-Up
Use the ÏÐ buttons to highlight the required menu option
and then press the button to select it.
3.3.3.1 Output Set-Up
The display presents a menu of parameter options along with their current settings.
[Release Settings]
ACTUATOR: SOLENOID .
COUNTDOWN AUTO: 0
COUNTDOWN MAN : 0
RELEASE PERIOD: 0
MINS TO RESET : 0
Use the ÏÐ buttons to highlight the required option and
then press the button to select it.
The table below details each available option.
Parameter Comments / Description Options Default
Setting
ACTUATOR Specifies the type of actuating devices connected to the
output.
METRON
SOLENOID
NOT
LEARNT
COUNTDOWN AUTO Specifies the delay timer before activating the actuator
output when the condition originates from AFD Zone
inputs.
0 – 60 Seconds
30
COUNTDOWN MAN Specifies the delay timer before activating the actuator
output when the condition originates from any manual
trigger input.
0 – 60 Seconds
30
RELEASE PERIOD Specifies the duration of the actuating output signal.
0 – 600 Seconds
300
MINS TO RESET Specifies the minimum time that must elapse before a
reset can be performed after the activation condition has
been established.
0 – 30 Minutes
10
HELD COUNTDOWN Specifies whether the countdown time will restart or will
continue for the remaining duration when the hold
activation is removed.
RESTART COUNT
SUSPEND COUNT
13
CONTINUE COUNT
RESTART
IN COUNTDOWN Specifies whether a RESET can be performed during the
countdown period.
ALLOW RESET
14
PREVENT RESET
PREVENT
12
The mark to space ratio of the HOLD PULSE signal should be configured to create a different pattern to the standard
Alert PULSE (1s ON / 1s OFF) pattern.
13
This setting is not in accordance with BS EN 12094-1: 2003.