3.3.1 Detection Zones
This menu configures each of the three detection zone input circuits. Highlight the DETECTION
option and press the button. The following Zone Select Menu will be shown.
[Zone Select]
Zone 1 .
Zone 2
Zone 3
Use the ÏÐ buttons to highlight the required zone and
then press the button to select it.
A menu of parameters is then presented for the selected
zone.
[Zone 1 Settings]
SNDR DELAY : 0 .
VERIFY TIME : 0
I.S. ZONE : NO
SHORT=ALARM : NO
NON-LATCH : NO
Use the ÏÐ buttons to highlight the required parameter
and then press the button to select / change it.
The table below details the parameters can be adjusted:
Parameter Comments / Description Options Default
Setting
SNDR DELAY Determines if the sounders are to be delayed before operating
when the panel detects a fire alarm from this zone.
0 – 600 seconds
0
VERIFY TIME Determines the minimum time that the circuit must be in the
alarm condition before an alarm condition is registered.
0 – 30 Seconds
0
I.S. ZONE? Determines whether the circuit is for use with Intrinsic Safety
Barriers.
NO / YES
NO
SHORT=ALARM? Determines if a short circuit is to be treated as an alarm
condition. If selected, the short circuit supervision on this circuit
is disabled. Normally, AFD or MCP devices will switch the circuit
into the alarm state via a 270-470 resistor / equivalent load.
NO / YES
NO
NON-LATCH? Determines if the panel should automatically reset from the
alarm condition if the alarm is cleared.
NO / YES
NO
3.3.2 Alarms
This menu configures each of the three alarm output circuits. Highlight the ALARM OUTPUTS
option and press the button. The following Sounder Select Menu will be shown.
[Sounder Select]
Sounder-1 .
Sounder-2
Sounder-3
PULSE PATTERN
Use the ÏÐ buttons to highlight the required sounder (or
the pulse pattern option) and then press the button to
select it.
A menu of parameters is presented for the selected
sounder.
3.3.2.1 Sounder Configuration
[Zone 1 Settings]
ZONE1 FIRE: ON .
ZONE2 FIRE: ON
ZONE3 FIRE: ON
STAGE-1 : ON
COUNTDOWN : ON
Use the ÏÐ buttons to highlight the required parameter
and then press the button to select / change it.
The table below details the parameters can be adjusted: