Page 29 of 42
3.3.3.4 Release Signal Termination (Test Function)
Section 4.21.5
A special Engineer function is provided to terminate an extended active extinguishing
control signal for the purposes of testing the system. This is provided at Level 2 using
the EXTINGUISHING menu option. When prompted, enter the Level 3 password
and a further option (STOP RELEASE: YES) is provided in the menu. Highlight this
option and press the button to turn off the extinguishing control signal output.
3.3.4 Inputs
The display presents a list of the programmable inputs along with their current settings.
[Input Settings]
PROG INPUT 1: .
NOT IN USE .
PROG INPUT 2:
NOT IN USE
PROG INPUT 3:
Use the ÏÐ buttons to highlight the required input and
then press the button to select / change it.
The table below details each available input and the
programmable settings.
The default setting for all inputs is NOT IN USE.
Inputs Setting Options Comments
PROG INPUT 1
NOT IN USE
The Input is not used.
PROG INPUT 2
SOUND ALARMS
Activating an input with this setting will cause all sounder outputs to turn ON.
PROG INPUT 3
SILENCE ALARMS
Activating an input with this setting will cause all sounder outputs to be Silenced.
PROG INPUT 4
RESET
Activating an input with this setting will cause the panel to be reset (if permitted).
KEY-SWITCH 1
EXT. FAULT
Activating an input with this setting will register a fault condition on the panel.
KEY-SWITCH 2
MANUAL TRIGGER
Activating an input with this setting will initiate the manual release activated
condition.
PRESSURE
Activating an input with this setting will register a pressure warning condition.
VALVE MON
Activating an input with this setting will register a Valve Monitor warning
condition.
MODE SELECT
Activating an input with this setting will select MANUAL ONLY mode. Note: When
multiple inputs are defined as mode select, then any switch in the active state will
set the system into MANUAL ONLY mode.
HOLD
Activating an input with this setting will stop the activated condition countdown
timer preventing the release of the extinguishant.
ABORT
Activating an input with this setting will abort the activated condition.
LEVEL-2 ACCESS
Activating an input with this setting will enable Level-2 Control Keys and Menu
functions. A password is not required.
START EXTRACT
Activating an input with this setting will turn on any output configured as an
Extract output. The output will remain on for the programmed time.
KEEP EXTRACT ON Activating an input with this setting will turn on any output configured as an
Extract output. The output will remain on irrespective of any programmed
operation or times.
3.3.5 Outputs
The display presents a list of the programmable outputs along with their current settings.
[Prog. Outputs]
RELAY 1 .
> NOT IN USE .
RELAY 2
* GENERAL FAULT
AUX RELAY 1
Use the ÏÐ buttons to highlight the required output and
then press the button to select / change it.
The table below details each available output and the
programmable settings available. The output can also be
configured as an INVERTED output (indicated by an *
character. In this mode, it is normally turned on and will
turn off when the applicable cause & effect occurs.