[Output Settings]
MODE: .
NOT IN USE .
INVERTED: NO
Use the ÏÐ buttons to highlight the required option and
then press the button to select / change it.
The default settings are as follows:
RELAY 1: STAGE-1 [INVERTED = NO]
RELAY 2: RELEASED [INVERTED = NO]
AUX RELAY 1 – 8: NOT IN USE [INVERTED = NO]
SWITCHED AUX: RESET [INVERTED = YES]
Outputs Setting Options Comments
RELAY 1
NOT IN USE The Output is not used and will not activate.
RELAY 2
FOLLOW SOUNDER 1 The output is activated when Sounder 1 is activated.
AUX RELAY 1
FOLLOW SOUNDER 2 The output is activated when Sounder 2 is activated.
AUX RELAY 2
FOLLOW SOUNDER 3 The output is activated when Sounder 3 is activated.
AUX RELAY 3
GENERAL FIRE The output is activated if any fire condition event occurs.
AUX RELAY 4
GENERAL FAULT The output is activated if any fault condition event occurs.
AUX RELAY 5
STAGE-1 The output is activated when a first stage alarm is recognized.
16
AUX RELAY 6
STAGE-2 The output is activated when a second stage release is recognized and the
actuator output is due to be operated.
AUX RELAY 7
RELEASED The output is activated when the release of extinguishant has been completed.
AUX RELAY 8
ON HOLD The output is activated when the release of extinguishant has been held.
SWITCHED AUX
ABORTED The output is activated when the release is aborted. It remains in this state until
the panel is reset.
MANUAL MODE The output is activated when the manual only mode is selected. (In the off
position the output indicates auto+manual).
VALVE CLOSED The output is activated when the valve monitor is active.
RESET The output is activated for approximately 10-15 seconds when the panel is
reset.
ZONE1 or STAGE-2 The output is activated when a second stage release is recognized OR the fire
alarm is from Zone 1.
ZONE2 or STAGE-2 The output is activated when a second stage release is recognized OR the fire
alarm is from Zone 2.
ZONE3 or STAGE-2 The output is activated when a second stage release is recognized OR the fire
alarm is from Zone 3.
EXTRACT The output is activated when the extract phase is in process.
TEST MODE The output is activated when any of the zones are in a test state.
3.3.5.1 Switched AUX Output
The Switched AUX Output is normally turned on and will turn off for about 5 seconds when the
panel is reset. This is useful for resetting conventional beam detectors, etc.
SWITCHED AUX: RESET [INVERTED = YES]
The output can alternatively be programmed to turn on when specific conditions occur to power
external equipment. For example, turn on when Stage 1 is active.
SWITCHED AUX: STAGE-1 [INVERTED = NO]
16
NOTE: Stage-1 will also be activated as soon as an immediate Stage-2 condition (i.e. manual release or single zone fire
alarm activation) occurs.