EN 12094-1: 2003
Electrical automatic control and delay device
Environmental class: A
1 Flooding Zone
CO
2
Low pressure
CO
2
High pressure
Inert gas systems
Provided options:
- Delay of extinguishing signal
- Monitor Flow of Extinguishing Agent
- Monitoring of status of components
- Emergency Hold Device
- Control of flooding time: 0 – 600s
- Manual Only Mode
- Triggering Signals to Equipment within the System
- Triggering Signals to Equipment outside the System
- Emergency Abort Device
- Activation of Alarm Devices with Different Signals
Response delay activated condition maximum 3s
Response delay triggering of outputs maximum 1s
EN54-2: 1997 +A1
Control and indicating equipment for fire detection and fire
alarm systems for buildings
Provided options:
- Outputs to Fire Alarm Devices
- Alarm Counter
- Test Condition
EN54-4: 1997 +A2
Power supply equipment for fire detection and fire alarm
systems for buildings