NOTE:
THIS PARAGRAPH IS EXCLUSIVELY
FOR THE TECHNICAL AFTER-SALES
SERVICE, OR WHOEVER IN AUTHO-
RITY.
This allows to modify the TECHNICAL
menu parameters listed below.
To access the menu, enter the INFO
menu and hold the
+ keys
down for 3 seconds.
To exit the TECHNICAL mode, press the
key.
Scroll the menu using the
and
keys. To modify the parameters use the
and keys.
CHRONO 19 TECHNICAL MENU
CODE CODE PARAMETER DEFAULT RANGE NOTES
Set AC
Water Set Point [°C] 15 0..25
Set point for plant water tempe-
rature and for dehumidification
consent
Set Hc Humidity Set Point [rH%] Comfort 65 10..100
Adjustment set point for Com-
fort humidity
Set HE
Humidity Set Point [rH%] Economy 65 10..100
Adjustment set point for Eco-
nomy humidity
TYP 3 Ch 3 B3 Probe type 0 0..1
0 = probe deactivated
1 = Coil Water Temperature
(WS)
Dif H
Differential for Dehumidification [rH%] 10 0..30 Differential for dehumidification
CAL A
Terminal temperature probe calibration
[°C]
0 -5..+5
Calibration of the temperature
probe present on the terminal
CP ON
Cycle CP 300” [s] 24 24..60
It is expressed in tenths of
seconds (240”..600”)
CP DEL
Delay CP 30” [s] 30 10..60
Auto
Automatic Restart 0 0..1
0
no restart
1
automatic restart
DEFMi
Time between two defrosts (min) 30 5..50 Time between two defrosts
DEFMa
Defrost duration [min] 5 1..15 Duration of the defrost
CAL H
Terminal humidity probe calibration [%rH] 0 -10..+10
Calibration of the humidity pro-
be present on the terminal
Delay
Delay FAN 10” [s] 30 5..60