EasyManuals Logo

AERMEC DMP User Manual

AERMEC DMP
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #8 background imageLoading...
Page #8 background image
8
(1) Room temperature 26 °C relati-
ve humidity 65%, coil inlet water
temperature 15°C. Minimum
fan speed.
(2) Maximum conditions: Room tem-
perature 35 °C relative humidity
80%, coil inlet water temperatu-
re 15°C. Minimum fan speed.
(3) Sound pressure level measured
in free field at 1 m from the unit,
directionality factor Q=2, accor-
ding to ISO 3746, minimum fan
speed.
(4) Room temperature 15 °C, coil
inlet water temperature 35 °C.
Minimum fan speed.
DMP20
REFRIGERANT R134a
Gas refrigerant load kg. 0,23
Nominal dehumidification capacity 1 l/24h 20
Nominal power 1W 340
Nominal current 1A 2,3
Dehumidification capacity 2 l/24h 49
Input power 2W 390
Power supply V/Ph/Hz 230/1/50
Nominal current A 2,5
Peak current A 4
Nominal water flow rate l/h 17 0
Pressure drops kPa 7
Heating capacity produced - normal heating conditions 4W 1010
Input power 4W 25
Selectable fan speed 3
Air flow rate
(minimum speed)
m
3
/h
200
(average speed) 300
(maximum speed) 380
SOUND DATA
Sound Pressure 3 dB(A) 33
External installation DIMENSIONS
Height mm 590
Width mm 750
Length mm 210
WEIGHT kg 36
5. TECHNICAL DATA
843
771
750
761
678
606590
596
8
18
227
210
FRAME (DMP20GL MANDATORY ACCESSORY)
PANEL CLOSURE
(DMP20GL MANDATORY ACCESSORY)
CASSAFORMA SYSTEM
(DMP20GL MANDATORY ACCESSORY)
DPM20

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC DMP and is the answer not in the manual?

AERMEC DMP Specifications

General IconGeneral
BrandAERMEC
ModelDMP
CategoryDehumidifier
LanguageEnglish

Related product manuals