Mini Power Post™ Monitoring System - USER GUIDE
Pump Alarms (continued)
HIGH AMP ALARM
A high amp alarm event will occur when the current sensed on
the pump input during a pump run event is equal to or greater
than the congured high amp threshold setting, factory set to
15 Amps.
The high amp alarm will not be activated during the initial startup
of a pump run event, even if the high amp threshold is exceeded
to account for high amp draw during pump startup. The high
amp threshold is deactivated as soon as the current sensed on
the pump is less than the programmed setting.
The purple and blue LEDs will illuminate inside the top cover of
the enclosure and alternate every second. The OLED screen
will display a HIGH AMP ALARM event. The alarm condition
will clear once the system no longer detects a high amp event.
Use the menu keypad to access the high amp alarm information
below while the pump is running or when the system is idle.
See pages 21, 25, and 29 for detailed information and display
screens.
High Amp Event Counter - Records each high amp
event.
High Amp Elapsed Time - Records the total run time of
each high amp event including: last, average, maximum,
and minimum of the last 10 extended pump run cycles.
High Amp, Amp Detection - Records the amps each
time a high amp event occurs including: last, average,
maximum, and minimum of the last 10 pump cycles.
High Amp Setting - Use the menu keypad to change the
high amp factory setting of 15 Amps. See page 21 for
detailed information.
All Data Stored in Two Formats
i. Resettable; Reset all data to zero.
ii. Non-Resettable; All lifetime data is stored.
‹ ‹ ‹ Alternating LEDs › › ›

Other manuals for Alderon Industries Mini Power Post MPMS-0001

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Alderon Industries Mini Power Post MPMS-0001 and is the answer not in the manual?

Alderon Industries Mini Power Post MPMS-0001 Specifications

General IconGeneral
BrandAlderon Industries
ModelMini Power Post MPMS-0001
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals