Serial Communications
B-9
Table B.4 Parameter Grouping/User Settings
(continued)
Group Parameter Name
Parameter
Number
Display
Units
Drive Units
Scale Factor ➁
Minimum Maximum Factory Setting
User’s
Setting
Run On Power Up 14 Text ➀ 1 –– –– Disabled
Reset/Run Tries 85 Numeric 1 0 9 0
t
Reset/Run Time 15 Seconds 100 0.5 30.0 1.0
lect
S Curve Enable 57 Text ➀ 1 –– ––– Disabled
Sel
S Curve Time 56 Seconds 10 0.0 300.0 0.0
re
Language 47 Text ➀ 1 –– –– Appropriate Lang.
atu
Cable Length 143 Text ➀ 1 –– –– Short
Fe
Rated Slip 146 Hz 10 0.0 5.0 2.0
Slip Comp Adder 148 Hz 100 0.00 5.00 ––
IR Comp % 147 % 1 0% 150% Drive Size Depend.
Output 1 Config 90 Text ➀ 1 –– –– Faulted
t
g
Output 2 Config 91 Text ➀ 1 –– –– Running
tpu
nfi
Analog Out Sel 25 Text ➀ 1 –– –– Frequency
Ou
Co
Above Freq Val 77 Hz 1 0 400 0
Above Curr Val 142 % 1 0 150% of Drive Rated Current (DRC) 0
Fault Buffer 0 86 Numeric 1 –– –– ––
Fault Buffer 1 87 Numeric 1 –– –– ––
ts
Fault Buffer 2 88 Numeric 1 –– –– ––
aul
Fault Buffer 3 89 Numeric 1 –– –– ––
F
Clear Fault 51 Text ➀ 1 –– –– Ready
Cur Lim Trip En 82 Text ➀ 1 –– –– Default Run
Line Loss Fault 40 Text ➀ 1 –– –– F03 Enable
Flt Clear Mode 39 Text ➀ 1 –– –– Enabled
➀ Refer to Table B.1 on pages B-13, B-14 and B-15 for the numerical equivalent of the text descriptions.
➁ Refer to page B-2.