Chapter 10 Operate the Module
Figure 94 - Alarm Status
When selecting the appropriate alignment method, consider the following:
Static Alignment:
Each voted alarm can have only one enabled output: Alert, Danger, or
Trans d u c er Fau lt .
Alarm Statuses align one-to-one with the corresponding Voted Alarm:
Voted Alarm 0 -- > Alarm Status 0
Voted Alarm 1 -- > Alarm Status 1
Voted Alarm 12 -- > Alarm Status 12
Relays are associated with an Alarm Status only if it references a Voted
Alarm.
Relays that are configured to actuate on Fault (only) do not have an
associated Alarm Status.