Rockwell Automation Publication 1444-UM001D-EN-P - June 2018 449
CIP Objects Appendix A
19 Get V Alarm Form SINT Defines form of alarm. Alarm form option
20 Get V Alarm Type SINT Defines behavior
regarding TX OK state.
Alarm type
options
21 Get V Alarm Processing
Mode
SINT Defines alarm
processing mode to be
Normal, Adaptive, or
Profile.
Alarm processing
options
Alarm Thresholds Group of eight configuration attributes.
24 Get V Low Alert
Threshold
REAL Defines low alert
threshold limit that is
used for Under
Threshold and Window
alarm types.
Range: -
49000…48000
25 Get V High Alert
Threshold
REAL Defines high alert
threshold limit that is
used for Over Threshold
and Window alarm
types.
Range: -
48000…49000
26 Get V Low Danger
Threshold
REAL Defines low danger
threshold limit that is
used for Under
Threshold and Window
alarm types.
Range: -50000
…49000
27 Get V High Danger
Threshold
REAL Defines high danger
threshold limit that is
used for Over Threshold
and Window alarm
types.
Range: -
49000…50000
32 Get V Hysteresis SINT The amount on the safe
side of a threshold by
which the value must
recover to clear the
alarm.
Range: 0…20 %
33 Get V Delay/Sustain
Time (Alert)
DINT Duration that a
measurement alarm
input must be
continuously present
before being reported
as an Alert alarm event
Individual delays
are an integer in
ms
Range: 0…65500
34 Get V Delay/Sustain
Time (Danger)
DINT Duration that a
measurement alarm
input must be
continuously present
before being reported
as a Danger alarm
event.
Individual delays
are an integer in
ms
Range: 0…65500
35 Get V Alarm Multiplier REAL Indicates how the
thresholds are adjusted
when the alarm
(threshold) multiplier
function is invoked.
1: in effect
disabled
>1: alarm less
likely
<1: alarm more
likely
Range: 0.01…to
100
Adaptive Monitoring Group of eleven configuration attributes.
40 Get V Adaptive
Monitoring Source
INT The data source for the
control variable.
Source selection
Table 181 - Instance Attributes (continued)