Publication 1734-UM006B-EN-P - August 2005
1-8 About the Modules
New Data Indicator
A two-bit counter, C1 & C0, updates every time an "event" occurs,
indicating that new data is available in the Stored/Accumulated Count
words. Definitions for events are as follows.
Any active gate transition in any of the Store Count (Counter or
Encoder) modes
The end of the gate sample period in either the Period mode or
Rate mode
The end of the programmed sample period in the Rate
Measurement mode.
To use these bits reliably, acquisition of data from the Counter Module
must occur faster than the events, which cause C1/C0 to increment.
When C1/C0 is updated, a Change Of State (COS) message can be
sent.
Default Configuration
The module's default configuration on startup is as follows.
Counter Mode
50Hz filter on A, B and Z
No time base
Rollover = 0x00FFFFFF
Preset = 0
No scalar
Counter Control Safe State = 0
To modify the default settings to those required for your application,
refer to the Input and Output section of this manual.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1734-IK and is the answer not in the manual?

Allen-Bradley 1734-IK Specifications

General IconGeneral
BrandAllen-Bradley
Model1734-IK
CategoryMedia Converter
LanguageEnglish

Related product manuals