Rockwell Automation Publication 5000-UM005B-EN-P - November 2015 117
Calibrate the Module Chapter 7
11. Click Next.
The One at a Time High Reference Results dialog box appears and
indicates the status of the channel after calibrating for a high reference
12. If the status is OK, click Next.
If the status reports an error, return to
step 11 until the status is OK.
13. When the Calibration Completed dialog box appears, click Finish.