128 Rockwell Automation Publication 825-UM004D-EN-P - November 2012
Chapter 9 825-PDN DeviceNet Communication Card
28. Select OK.
29. Moving cursor into the grid, place Aux
Out 5 to the right of the AND
function block
30. Co
rrect the Fault Input to th
e Aux Out 5.
31. Do one of the following:
• In the toolbar, select To o ls .
• From the pull-down menu, select Logi
c Verify.
32. To toggle out of edit mode if you are online with a device, select To o
l s .
33. After selecting Edit
from the main menu, select Download from the pull-
down menu (right corner of the toolbar).
34. When the download is successful, select OK.
35. From the same pull-down menu, select Log
ic Enable On.
36. The 825-P Modular Protection System is now programmed and the logic
is a
ctive.
NOTE: The PLC key switch must be in the Program position. If not, the download does not occur and
a generated error occurs.