Publication 1756-RM084F-EN-P - July 2002
Creating a Complete Import/Export File 3-37
DF1
(continued)
TransmitRetries
Specify the number of attempted retires (0-255) without getting an
acknowledgement before the message is deemed undeliverable.
Specify:
TransmitRetries :=
value
StationAddress
Specify the current station link address (0-254).
Specify:
StationAddress :=
value
ReplyMessageWait
Specify the time the master waits after receiving an
acknowledgment to a master-initiated message before polling the
slave for a response. Enter an increment of 20ms (0-65535).
Specify:
ReplyMessageWait :=
value
PollingMode
Specify the polling mode. Enter on of these:
1 for Message Based (slave can initiate messages)
2 for Message Based (slave cannot initiate messages)
3 for Standard (multiple message transfer for node scan)
4 for Standard (single message transfer per node scan)
Specify:
PollingMode :=
value
MasterMessageTransmit
Specify when the master transmits. Enter 0 to transmit between
station polls; enter 1 to transmit in poll sequence.
Specify:
MasterMessageTransmit :=
value
NormalPollNodeFile
Specify the tag name of the structure that contains the normal poll
node list. Or enter <NA>.
Specify:
NormalPollNodeFile :=
value
NormalPollGroupSize
Specify the total number (0-255) of active stations polled from the
poll list.
Specify:
NormalPollGroupSize :=
value
PriorityPollNodeFile
Specify the tag name of the structure that contains the priority poll
node list. Or enter <NA>.
Specify:
PriorityPollNodeFile :=
value
ActiveStationFile
Specify the tag name of the structure that contains the status
(active or non-active) of each node. Or enter <NA>.
Specify:
ActiveStationFile :=
value
SlavePollTimeout
Specify the amount of time the master waits for an
acknowledgement to a message sent to a slave. Enter an increment
of 20ms (0-65535).
Specify:
SlavePollTimeout :=
value
EOTSuppression
Specify whether to enable EOT suppression. Enter 0 to disable;
enter 1 to enable.
Specify:
EOTSuppression :=
value
MaxStationAddress
Specify the maximum station address (0-31).
Specify:
MaxStationAddress :=
value
TokenHoldFactor
Specify the token hold factor (1-4).
Specify:
TokenHoldFactor :=
value
ExtendedDevice
none none
FaultLog
none none
ICP
none none
PCCC
none none
Redundancy
none none
Object: Attribute: Description: