Rockwell Automation Publication 2198-UM002G-EN-P - February 2019 133
Connect the Kinetix 5700 Drive System Chapter 5
This impedance-grounded power configuration (Figure 85) does not provide a
neutral ground point.
Figure 85 - Impedance-grounded Power Configuration (WYE secondary)
(1) 2198-RPxxx power supply has the ground jumper removed. 2198-xxxx-ERSx inverters have the ground jumpers removed.
ATTENTION: Ungrounded systems do not reference each phase potential to
a power distribution ground. This can result in an unknown potential to earth
ground.
L3
L2
L1
L3
L2
L1
Transformer
Three-phase
Input VAC
Phase Ground
Transformer (WYE) Secondary
Ground Grid or
Power Distribution Ground
Connect to drive
module ground stud.
Circuit
Protection
2198-RPxxx
(1)
Regenerative Bus Supply
(bottom view)
M1
Contactor
Bonded Cabinet
Ground
IMPORTANT If you determine that you have impedance-grounded power distribution in
your facility, you must remove the ground screw in your regenerative power
supply, iTRAK power supplies, and dual-axis inverters, and the ground
jumper in each of your single-axis inverters.
Refer to Ground Screw/Jumper Settings
on page 135 for more information.