94 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Chapter 5 Connect the Kinetix 6200 and Kinetix 6500 Drive System
Figure 48 - Corner-grounded Power Configuration (Delta Secondary)
Figure 49 - Impedance-grounded Power Configuration (WYE Secondary)
Refer to Appendix A on page 231, for input-power interconnect diagrams with
and without the LIM module.
L3
L1
L2
1 2
DC-
DC+
L3
L2
L1
CONT EN-
CONT EN+
CTRL 2
CTRL 1
1 2
1 2 3 4 5 6
W
V
U
MBRK -
MBRK +
COM
PWR
DBRK -
DBRK +
1 2 3 4
1 2 3 4 5 6
Transformer (Delta) Secondary
Bonded Cabinet
Ground
Transf or me r
Ground Grid or
Power Distribution Ground
Connect to power rail ground stud.
Three-phase
AC Line Filter
M1
Contactor
Bulletin 2094
IAM Power Module, Top View
Circuit
Protection
L3
L2
L1
1 2
DC-
DC+
L3
L2
L1
CONT EN-
CONT EN+
CTRL 2
CTRL 1
1 2
1 2 3 4 5 6
W
V
U
MBRK -
MBRK +
COM
PWR
DBRK -
DBRK +
1 2 3 4
1 2 3 4 5 6
Transformer (WYE) Secondary
Bonded Cabinet Ground
Transformer
Ground Grid or
Power Distribution Ground
Connect to power rail ground stud.
Three-phase
AC Line Filter
M1
Contactor
Bulletin 2094
IAM Power Module, Top View
Circuit
Protection
Three-phase
Input VAC
Phase Ground
IMPORTANT Even though impedance-grounded and corner-grounded power
configurations have a ground connection, treat them as ungrounded when
installing Kinetix 6000 drive systems.