Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 95
Connect the Kinetix 6200 and Kinetix 6500 Drive System Chapter 5
Ungrounded Power Configurations
The ungrounded power configuration (Figure 50) does not provide a neutral
ground point. Ungrounded, impedance-grounded, and corner-grounded
power configurations are allowed, but you must move a jumper (internal to the
IAM power module) across a 120 k resistor. The IAM power module ground
jumper (default configuration) is set for grounded power distribution.
Figure 50 - Ungrounded Power Configuration
Refer to Appendix A on page 231, for input-power interconnect diagrams with
and without the LIM module.
IMPORTANT If you determine that you have ungrounded, impedance-grounded, or
corner-grounded power distribution in your facility, you must move the
ground jumper (configured for grounded power) to the ungrounded power
position inside the IAM power module.
Refer to Set the Ground Jumper in Select Power Configurations on page 97
for more information.
L3
L2
L1
1 2
DC-
DC+
L3
L2
L1
CONT EN-
CONT EN+
CTRL 2
CTRL 1
1 2
1 2 3 4 5 6
W
V
U
MBRK -
MBRK +
COM
PWR
DBRK -
DBRK +
1 2 3 4
1 2 3 4 5 6
Transformer
Three-phase
Input VAC
Chassis Ground
Bonded Cabinet
Ground
Ground Grid or
Power Distribution Ground
Connect to power rail
ground stud.
M1
Contactor
Bulletin 2094
IAM Power Module, Top View
Transformer (Delta) Secondary
Circuit
Protection
ATTENTION: Ungrounded systems do not reference each phase potential to
a power distribution ground. This can result in an unknown potential to
earth ground.