EasyManuals Logo

Allen-Bradley PowerFlex 400 User Manual

Allen-Bradley PowerFlex 400
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
1-2 Main Input Disconnect Package (Style A/M)
Rockwell Automation Publication 22C-IN002E-EN-P - November 2010
Main Fuses (FU1-FU3)
Input line branch circuit protection fuses must be used to protect the input
power lines. If input fuses are not provided with your drive, recommended
fuse values are shown in Table 1.A
. The input fuse ratings listed in Table
1.A are applicable for one drive per branch circuit. No other load may be
applied to that fused circuit.
The recommended fuse type for all PowerFlex 400 Drive Packages for Fan
& Pump Applications is UL Class J.
Table 1.A Fuse Recommendations
!
ATTENTION: Most codes require that upstream branch circuit
protection be provided to protect input power wiring. Install the
fuses recommended in Table 1.A
. Do not exceed the fuse ratings.
Failure to observe this precaution could result in damage to, or
destruction of, the equipment.
Drive Rating Fuse Rating
Input Voltage kW Hp Amps
208V AC – 3-Phase 2.2 3.0 20
3.7 5.0 20
5.5 7.5 35
7.5 10 40
11 15 80
15 20 100
18.5 25 125
22 30 150
30 40 200
37 50 250
460V AC – 3-Phase 2.2 3.0 10
4.0 5.0 15
5.5 7.5 20
7.5 10 20
11 15 35
15 20 35
18.5 25 60
22 30 70
30 40 80
37 50 100
45 60 150
55 75 175
75 100 200
90 125 250
110 150 350
132 200 400
160 250 500
200 300 600
250 350 700

Table of Contents

Other manuals for Allen-Bradley PowerFlex 400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 400 and is the answer not in the manual?

Allen-Bradley PowerFlex 400 Specifications

General IconGeneral
Input Voltage200-240VAC, 380-480VAC, 500-600VAC
Output Voltage0-Input Voltage
Output Frequency0-400 Hz
CommunicationEtherNet/IP
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short Circuit
Operating Temperature-10°C to 50°C (14°F to 122°F)
Storage Temperature-40°C to 70°C (-40°F to 158°F)
Humidity5-95% non-condensing
Enclosure RatingIP20
Horsepower0.5-20 HP
Control MethodV/Hz, Sensorless Vector Control