01
DATEREV. BY ECN/CR. NO.
APPROVAL
DESIGN REVIEW
FOR MANUFACTURING
AS SHIPPED
AS COMMISSIONED
BYDATE
SH.NEXT
NO.SH.
-
DWG.ENG.
TITLE
CHK. BY
NO.DATE DATE
DR. BY
DATE
THIS DRAWING IS THE PROPERTY OF ROCKWELL AUTOMATION, INC.
OR ITS SUBSIDIARIES AND MAY NOT BE COPIED, USED OR DISCLOSED FOR ANY
PURPOSE EXCEPT AS AUTHORIZED IN WRITING BY ROCKWELL AUTOMATION, INC.
11
INTER-CONNECT DRAWING (CIRCUIT BREAKER)
PF400, 250-350HP/460VAC, NEMA1
STYLE A, FRAMES G & H, CONTROL
97D01889
REH/ACI
10/9/06
AWR/ACI
10/9/06
AWR/ACI
10/9/06
G
L3
INCOMING
3
f POWER
L2
L1
MAIN
CIRCUIT
BREAKER
GROUND
CONNECTIONS SUPPLIED BY CUSTOMER
OPENING OF THE FREEZE/FIRE INTERLOCK
WILL REQUIRE MANUAL RESET.
1
10
OPTO COMMON
AUTO
DIGITAL INPUT 4 (COMM PORT)
DIGITAL COMMON
DIGITAL INPUT 3 (CLEAR FAULT)
DIGITAL INPUT 2 (LOCAL)
DIGITAL COMMON
DIGITAL INPUT 1 (PURGE)
SOFTWARE ENABLE
FUNCTION LOSS
S TATS
FREEZE/FIRE
AUTO START
INTERLOCKS
1
RUN/FWD
324
PURGE
HAND
57689
10V 20MA
AO1 AO2
10V 20MA
CONTROL BOARD
S/L2
T/L3
R/L1
GP2P1
RJ-45 SHIELD
#2 RELAY N.C.
#2 RELAY COMMON
#2 RELAY N.O. (MOTOR RUNNING)
#1 RELAY N.C.
#1 RELAY COMMON
OPTO OUTPUT (AT FREQUENCY)
ANALOG COM #2
#1 RELAY N.O. (READY/FAULT)
ANALOG INPUT #2
ANALOG OUTPUT #2 (OUTPUT CURRENT 0-10V)
ANALOG OUTPUT #1 (FREQUENCY 0-10V)
ANALOG COM. #1
ANALOG INPUT #1
SPEED REF. INPUT
0 TO +10VDC, 100KOHM
INPUT IMPEDANCE
R1
1
+
SPEED REF. INPUT
4-20MA, 250 OHM
INPUT IMPEDANCE
+
+ 24VDC
+ 10VDC
11 12 1413 15 1716 18 2019 R4R2 R3 R5 R6
10V 20MA10V 20MA
AI1
SNK
AI2
SRC
POWERFLEX 400
W/T3
V/T2
U/T1
MOTOR
T2
T3
T1
2
2
2
WHEN IN "AUTO MODE" SPEED REFERENCE WILL
COME FROM 0-10V SOURCE WIRED TO ANALOG
INPUT #1. IF 4-20mA SOURCE IS TO BE USED,
WIRE TO ANALOG INPUT #2 AND CHANGE PARAMETER
PO38 [SPEED REFERENCE] =3 "ANALOG In2".
DM1
CB1
34
IF FREEZE/FIRE STAUS INTERLOCK IS USED, THE
JUMPER WIRE FROM TERMINALS 1 TO 3 MUST BE REMOVED.
3
IF THE INTERLOCK CONTACT IS USED, THE JUMPER
FROM TERMINALS 1 TO 3 MUST BE REMOVED AND
THE JUMPER WIRE FROM TERMINALS 3 TO 11 SHOULD
4
BE RELOCATED TO CONNECT TERMINALS 1 TO 11.