Troubleshooting 4-7
Drive does not Start from Start or Run Inputs wired to the terminal block.
Drive does not respond to changes in speed command.
Cause(s) Indication Corrective Action
Drive is Faulted Flashing red status light Clear fault.
• Press and hold Up Arrow key for 
3 seconds.
• Cycle power
• Set A100
 [Fault Clear] to option 1 
“Clear Faults”.
• Cycle digital input if A051
 - A054 
[Digital Inx Sel] is set to option 7 
“Clear Fault”.
Incorrect programming.
• P036
 [Start Source] is set to 
option 5 “Comm Port”.
None Check parameter settings.
Incorrect input wiring.
See 1-22
 for wiring examples.
• 2 wire control requires Run 
Forward, Run Reverse or Jog 
input. 
• 3 wire control requires Start and 
Stop inputs
• Stop input is always required.
None Wire inputs correctly and/or install 
jumper.
If using the DriveGuard Safe-Off 
Option (Series B) board, verify that 
inputs are active.
Incorrect Sink/Source DIP Switch 
setting.
None Set switch to match wiring scheme.
Cause(s) Indication Corrective Action
No value is coming from the 
source of the command.
The drive “Run” indicator is lit 
and output is 0 Hz.
• Check b012
 [Control Source] for 
correct source.
• If the source is an analog input, 
check wiring and use a meter to 
check for presence of signal.
• Check b002
 [Commanded Freq] 
to verify correct command.
Incorrect reference source is 
being selected via remote 
device or digital inputs.
None • Check b012
 [Control Source] for 
correct source.
• Check b014
 [Dig In Status] to 
see if inputs are selecting an 
alternate source. Verify settings 
for A051
 - A054 [Digital Inx Sel].
• Check P038
 [Speed Reference] 
for the source of the speed 
reference. Reprogram as 
necessary.
• Review the Speed Reference 
Control chart on page 1-27
.