EasyManua.ls Logo

Allen-Bradley PowerFlex 40P - Basic Program Group

Allen-Bradley PowerFlex 40P
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Programming and Parameters 3-9
Basic Program Group
P031 [Motor NP Volts] Related Parameter(s): b004, A084, A085, A086, A087
Stop drive before changing this parameter.
Set to the motor nameplate rated volts.
Values Default: Based on Drive Rating
Min/Max: 20/Drive Rated Volts
Display: 1 VAC
P032 [Motor NP Hertz] Related Parameter(s): A084, A085, A086, A087, A090
Stop drive before changing this parameter.
Set to the motor nameplate rated frequency.
Values Default: 60 Hz
Min/Max: 15/500 Hz
Display: 1 Hz
P033 [Motor OL Current] Related Parameter(s): A055, A058, A061, A089, A090,
A098
, A114, A118
Set to the maximum allowable motor current.
The drive will fault on an F7 Motor Overload
if the value of this parameter is exceeded by 150% for 60
seconds.
Values Default: Based on Drive Rating
Min/Max: 0.0/(Drive Rated Amps × 2)
Display: 0.1 Amps
P034 [Minimum Freq] Related Parameter(s): b001, b002, b013, P035, A085,
A086
, A087, A110, A112
Sets the lowest frequency the drive will output continuously.
Values Default: 0.00 Hz
Min/Max: 0.00/500.0 Hz
Display: 0.01 Hz
P035 [Maximum Freq] Related Parameter(s): b001, b002, b013, P034, A065,
A078
, A085, A086, A087, A111, A113
Stop drive before changing this parameter.
Sets the highest frequency the drive will output.
Values Default: 60.00 Hz
Min/Max: 0.00/500.0 Hz
Display: 0.01 Hz

Table of Contents

Other manuals for Allen-Bradley PowerFlex 40P

Related product manuals