Programming and Parameters 3-13
Basic Program Group (continued)
P039 [Accel Time 1] Related Parameter(s): P038, P040, A051-A054,
A067
, A070-A077, A140-A147
Sets the rate of acceleration for all speed increases.
Values Default: 10.0 Secs
Min/Max: 0.0/600.0 Secs
Display: 0.1 Secs
Maximum Freq
Accel Time
Accel Rate
=
Speed
0
Time
P035 [Maximum Freq]
P039, A067,
E203 or E205
[Accel Time x]
P040, A068,
E204 or E206
[Decel Time x]
0
Acceleration
Deceleration
P040 [Decel Time 1] Related Parameter(s): P038, P039, A051-A054,
A068
, A070-A077, A140-A147
Sets the rate of deceleration for all speed decreases.
Values Default: 10.0 Secs
Min/Max: 0.0/600.0 Secs
Display: 0.1 Secs
Maximum Freq
Decel Time
Decel Rate
=
Speed
0
Time
P035 [Maximum Freq]
P039, A067,
E203 or E205
[Accel Time x]
P040, A068,
E204 or E206
[Decel Time x]
0
Acceleration
Deceleration
P041 [Reset To Defalts]
Stop drive before changing this parameter.
Resets all parameter values to factory defaults.
Options 0 “Ready/Idle” (Default)
1 “Factory Rset” After the reset function is complete, this parameter will set
itself back to “0”.
Causes an F48 Params Defaulted
fault.