Chapter VI Specified Function Introduction
95
6.3 Monitor and Display (Group P02)
Refer to Section 3.3 for function description about monitor and display.
6.4 I/O and Analog Control (Group P03)
Function
Code
Parameter Name
Attribute
Setting
Range
Unit
Factory
Defaults
P03.00
DO1 function and
enabled status setting
Power up
effective
0~3
256~259
-
0
Function Description:
Setting the function and enabled status of open collector OC output DO1..
The setting value can be obtained by adding enabled status settings and output function
settings together. If the setting value is not in the setting range, the system will retain
the last one.
Enabled status setting value:
0: Active High (Factory Defaults)
256: Active Low
Output Function Setting:
0: Servo Ready (S_RDY)
1: Servo Alarm (S_Alarm)
2: positioning completed/speed arrived
(P_CMP/V_CMP
3: Home
Examples for setting:
The output function wants to be set to servo alarm and active low, then the setting
value is 1+256=257.
Function
Code
Parameter Name
Attribute
Setting
Range
Unit
Factory
Defaults
P03.01
D02 function and
enabled status setting
Power up
effective
0~3
256~259
-
1
Function Description:
Refer to P03.00 for function description.