EasyManua.ls Logo

Alutech BV-5-868 - Setting Operation Parameters

Alutech BV-5-868
140 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BOOM BARRIER BV5868 2323
SETUP
7.2 SETTING OPERATION PARAMETERS
Table 15 shows descriptions of settings, values and factory-preset values upon delivery.
Anexample of setting is given in Table 5.
Table 15
MENU SETTING DESCRIPTION VALUES
FACTORY
SETTING
P1
F1
Select boom. The conguration is set to t
the eective length of the boom (Table 3). To
verify that the setting has been selected, see
sub-section 5 ‘Mains connection and open-
close setting’
no — not set
3.0 — 3…4 m
4.0 — 4…5 m
5.0 — 5…6 m
6.0 — 6 m
no.
Y
When P1F1 settings are changed, the factory-preset values of P5 and P6 menus are set
automatically
P3
F1
Manual operation mode. The movement is
performed when pressing and holding the
control device: OP and CL connection inputs
(Fig.37, terminal block 4). Commands from
remote controls and automatic movements are
not executed, SBS and ALR inputs do not work
no — disabled
on — enabled
no.
Y
In manual mode, the control devices must be located in a place that ensures a good visibil-
ity of the barrier area (boom movement). If access is attempted by unauthorized persons,
any operation by them must be made impossible, e.g. by installing a key switch
F3
Collective operation mode. Depending on
whether the mode is enabled or disabled,
the logic of SBS connection (Fig. 37, terminal
block4) and STEP-BY-STEP inputs of the
remote control (Table 6) will dier.
Enabled: when a command is executed,
the operation sequence will be as follows
Open — Close — Open — Close…
When opening, no commands are executed.
When closing, a command will cause the barri-
er to stop and subsequent full opening.
Disabled: when a command is executed,
the operation sequence will be as follows
Open— Stop — Close — Stop — Open…
no — disabled
on — enabled
no.
F4 Outputs on terminal block 5 (Fig.37)
no — disabled
01…16 — see details
in Table 16
no.
F5 Outputs on terminal block 6 (Fig.37)
F6 Outputs on terminal block 7 (Fig.37)
F7 Outputs on terminal block 8 (Fig.37)
F8
Functioning of SBS and OP inputs (Fig.37,
terminal block 4). When conguring the out-
puts of terminals 5–8 for two-way regulation
(values 05 and 06, Table 16), the SBS input can
be used for the ENTRY direction, the OP input
for the EXIT direction. STEP-BY-STEP or OPEN
commands correspond to those of the remote
control. (Table 6)
01
02
03
SBS step-by-step
OP OPEN
SBS step-by-step
OP OPEN
SBS step-by-step
OP OPEN
01.

Table of Contents