3A.2 Installation
3A.2.1 Mechanical installation
Do not mount the drive on surfaces subject to vibrations.
The installation environment shall be free of dust, metallic particles, suspension
oil, gas and sprays of corrosive liquids.
The drive shall always be mounted in the vertical position. Do not mount a unit with
an incline greater than + 30% from vertical.
If more than one drive is installed in the same enclosure, the drives shall be
positioned side by side
If a unit is installed above another it necessary to lead the out-coming cooling air
away from the unit above.
Example
.
The cooling of drive power components is accomplished through forced ventilation. Allow clearance around the drive for air circulation,
power cables, and access for maintenance operations.
3A.3.1.1 Clearances around the drive
The GT3000 fans are designed to provide adequate airflow for the
drive. When installing the unit, do not obstruct airflow path.
Figure 3A.3.1.1 Clearances Required Around the Drive
CAUTION
+104°F
Ta= +40°C
Air Baffle
Free space around the drive
Frame
A B1 B2
mm / in mm /in mm / in