3. Timer Mode
E. Led Signaling Chart
F. Troubleshooting
Prior to electrical troubleshooting, confirm that the mechanical system properly functions; i.e., that the pushbar fully retracts all latches and
the door opens freely. Refer to applicable 6000 Series Exit Device product instruction sheet to correct mechanical* installation issues.
IMPORTANT:
* ALWAYS disconnect power before making any mechanical adjustments to the system.
Signal
Dark / Unlit
Solid Light
Controller microprocessor is
not active
2 Flashes
Followed by Pause
Input voltage is dropping out
of operation range
Con rm connections and incoming power
Steady Flashing
Normal operation
Retractor sensor problem Call 1-800-810-9473 for assistance
Cycle device by closing the timer circuit.
Check wire run and power supply output
Cause Troubleshooting
The pushbar does not move when 24V input is applied:
Check inputs to confirm proper voltage and wiring orientation. When configured for the timer Mode, 24V must
be constantly applied and the timer circuit must be closed to cycle the device.
Remove end cap from pushbar and confirm that LED is blinking steadily when power is applied. If not, refer to
LED signaling.
The onboard timer duration adjustment is not working:
Remove power when making adjustments to time delay settings (DIP switches).
When a momentary signal is applied to timer circuit, circuit must be reopened for timer to function.
The pushbar does not fully retract or pushbar retracts completely and holds, but does not open door:
*Verify mechanical installation and correct as necessary:
Is excessive force required to depress the pushbar?
Are latches fully clearing the strikes when mechanically cycled?
The pushbar retracts electronically but does not release. System does not relock:
Confirm that Timer Mode contact is opened ( the pushbar will remain depressed until contact is opened and
delay has expired.)
Physically disconnect power from pushbar (While electronically retracted,) to verify if issue is mechanical.
Check for mechanical interference (e.g., warped door, lack of shims, misalignment of pushbar. etc.)
Rail behaves abnormally (multiple cycles, clicking, delay retraction, etc.):
If a momentary contact is applied to time circuit, adjust onboard timer to a longer duration.
Remove end cap from pushbar and confirm that LED is blinking steadily when power is applied. If not, refer to
LED signaling.
1-855-577-5078 Ext. 2 • www.accentra-assaabloy.com
6000 Series MELR