4. Optional "O" Trim Monitor Switch
For MELR applications using the optional “O” trim monitor switch,
the NO or NC output can be selected on the controller. Factory
preset is NO, however to change to NC perform the following:
1. Remove the controller for the exit device.
2. Move the trim monitor switch wire harness to the desired
configuration as shown in Figure 22.
3. Place the controller back into the Exit Device, ensuring that
the tab is attached to the Exit Device chassis.
NOTE:
Connector position is relative to the block.
“O” NO
“O” NC
Controller Unit
Trim Monitor Switch Wire Harness
Figure 21: Changing "O" Preset
1-855-577-5078 Ext. 2 • www.accentra-assaabloy.com
6000 Series MELR
Exit Devices
Installation Instructions
22
80-8150-0077-000 04/24