Grease change is performed during maintenance
- Generally after 4 to 6 years for modulating duty.
- Generally after 6 to 8 years if operated frequently (open-close duty).
- Generally after 10 to 12 years if operated infrequently (open-close duty).
We recommend replacing the seals when changing the grease.
Additional lubrication of the gear housing is not required during operation.
12.3. Disposal and recycling
Our devices have a long lifetime. However, they have to be replaced at one point in
time.The devices have a modular design and may, therefore, easily be separated
and sorted according to materials used, i.e.:
various metals
plastics
greases and oils
The following generally applies:
Greases and oils are hazardous to water and must not be released into the
environment.
Arrange for controlled waste disposal of the disassembled material or for sep-
arate recycling according to materials.
Observe the national regulations for waste disposal.
75
SA 07.2 SA 16.2/SAR 07.2 SAR 16.2 Control unit: electronic (MWG)
AC 01.2 Non-Intrusive HART Servicing and maintenance

Table of Contents

Other manuals for AUMA SA Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA SA Series and is the answer not in the manual?

AUMA SA Series Specifications

General IconGeneral
Torque range10 Nm to 32, 000 Nm
Protection classIP68
Ambient temperature+70°C
Voltage24V DC
CommunicationPROFIBUS DP, MODBUS RTU, Foundation Fieldbus
CertificationsATEX, IECEx, CSA, GOST, SIL
ControlLocal, Remote, Bus (PROFIBUS, MODBUS)

Related product manuals